Transformer Impedance (Percent Z): 6 Checks Before You Specify
Impedance is the one transformer number that decides two things at once: how much fault current the transformer lets through, and how far the voltage dips when a large motor starts. Datasheets quote a percentage — 4 %, 5 %, 6 % — without saying why. When a buyer writes “standard impedance”, the supplier picks the cheapest value, and the consequences show up years later as nuisance tripping or a stalled motor.
1. What percent Z actually controls
Percent impedance — transformer impedance expressed as a percentage — is the voltage applied to the primary, with the secondary shorted, to circulate rated current. One number sets four things:
- Fault current — the bolted-fault current is roughly rated current divided by percent Z. A 6 % unit passes about 16.7 times rated current into a dead short.
- Fault level at the LV busbar — which fixes the breaking capacity of every breaker downstream.
- Voltage regulation — the drop from no-load to full load, and the dip during motor starting.
- Mechanical forces — lower impedance means higher current and far higher winding forces.

2. Check one: fault current against downstream ratings
Start at the LV side and work backwards: the fault level must be matched to the main breaker’s breaking capacity and the busbar withstand.
| Percent Z | Fault current (× rated) | Fault level, 1000 kVA unit | Typical comment |
|---|---|---|---|
| 4 % | 25 × In | 25 MVA | Cheap windings, heavy fault current, strong enclosure needed |
| 5 % | 20 × In | 20 MVA | Common for small distribution units |
| 6 % | 16.7 × In | 16.7 MVA | IEC 60076 preferred series, widely available |
| 7 % | 14.3 × In | 14.3 MVA | Used where the LV board has limited breaking capacity |
| 8 % | 12.5 × In | 12.5 MVA | Higher regulation losses, usually a compromise |
On a 1000 kVA, 11 kV/0.415 kV unit, rated LV current is about 1391 A. At 6 % the bolted fault current is roughly 23 kA; at 4 %, 34.8 kA. That difference decides whether a standard 25 kA panel is acceptable or you are buying a 36 kA board — a real cost difference settled by one line in the datasheet. See also the temperature rise test guide.
3. Check two: voltage dip during motor starting
Impedance is also a voltage divider: motor inrush flows through it and the terminal voltage dips. Keep the dip under 10 to 15 %, or the contactor drops out and the motor never accelerates.
Two things make the dip worse — higher percent Z, and a motor that is large relative to the transformer. A 250 kW motor on 1000 kVA is already difficult: once the motor passes 25 to 30 % of transformer rating, accept a deeper dip, add a soft starter, or reduce impedance and re-check the fault level against the LV board.

4. Check three: parallel operation tolerance
Transformers paralleled on one busbar share load in inverse proportion to impedance. Two equal-rating units differing by more than about 10 % in percent Z leave the lower-impedance unit carrying a disproportionate share and running hotter. The usual specification:
- Same voltage ratio and vector group — non-negotiable.
- Percent Z within ±10 % of each other, preferably the same design.
- Similar X/R ratio, since the reactive share is what actually unbalances.
- Tap positions that let the ratio be matched at the operating point.
When matching an existing transformer, ask for the measured value from the routine test report, not the catalogue figure. Tolerance is commonly ±7.5 % to ±10 %, so two “6 %” units can be 5.5 % and 6.5 % — both in tolerance, 15 % apart.
5. Check four: losses, temperature and enclosure size
Lower impedance is not free. It buys fault headroom and better motor starting, and costs copper: bigger windings, heavier bracing, a different loss balance and a larger enclosure — which matters inside a compact substation where the footprint is fixed. IEC 60076-1 therefore lists preferred values; a “special” 3.5 % unit is a custom design at a custom price.
6. Checks five and six: standard values, and the datasheet wording
Check five: use a standard value unless there is a documented reason not to — tooling, test data and spares all follow the series.
Check six is the wording. A datasheet that says only “impedance: 6 %” invites delivery of anything inside tolerance. Write instead:
- Percent impedance at rated voltage and rated current, measured per IEC 60076-1, at a stated tap.
- Tolerance stated explicitly, e.g. ±7.5 % of the declared value, with the measured figure in the routine test certificate.
- The tap at which the value applies, because impedance shifts with tap.
- Vector group and voltage ratio on the same line, so the three cannot be quoted inconsistently.
- For parallel operation, the X/R ratio and the guaranteed impedance of each unit.
Quick reference for choosing: up to 630 kVA, 4 to 5 %; 800 to 2500 kVA, 6 % — the most widely tooled value, keeping LV fault levels inside standard 25 to 36 kA panels; larger units or a weak LV board, 7 to 8 % with the motor-starting penalty accepted.
For packaged units see the compact substation guide; for commissioning, the oil testing checks and the differential protection guide; for dry-type alternatives, the cast resin guide. Low voltage side practice is on our sister site.

FAQ
Is higher impedance always safer?
No. It lowers fault current, which helps the LV board, but deepens the motor-starting dip and raises regulation losses. The right value satisfies both the fault rating and the starting dip.
Can I parallel a 6 % transformer with a 5.5 % one?
Only if the difference stays within about 10 % and both share the same vector group and ratio. Use the measured values from test certificates, not catalogue figures.
Does percent Z change with tap position?
Yes, slightly. Values are quoted at the principal or middle tap, so state which tap applies.
How is impedance measured?
With the secondary short-circuited, reduced voltage is applied to the primary until rated current flows; that voltage as a percentage of rated voltage is the percent impedance.
Why do two identical transformers measure differently?
Manufacturing tolerance on windings, clearances and core geometry, within the ±7.5 % to ±10 % allowed on the declared value.
Does impedance affect the breaking capacity I need downstream?
Directly. Fault level sets the minimum breaking capacity of the main breaker and the busbar withstand, so fix impedance before ordering the LV panel.
About Electric-GS
Electric-GS is an OEM/ODM manufacturer of MV switchgear, RMUs, vacuum circuit breakers and distribution transformers in Yueqing, China. We build to IEC 60076 and IEC 62271, and every unit ships with a routine test certificate including measured impedance, no-load and load losses. For impedance selection support or a quotation, contact info@electric-gs.com or WhatsApp +86 135 8897 8050.