GSRM6-40.5 36KV Gas Insulated Switchgear

GSRM6-40.5 36KV Gas Insulated Switchgear

GSRM6-40.5 33KV 36KV Series are a new type SF6 gas-insulated compact switchgears. Circuit breakers, disconnectors, and other parts are enclosed in 3mm-thick metal containers filled with a low-pressure SF6 gas. Thus, the equipment is compact, reliable, and safe; free of environmental impacts, free maintenance and long service life, etc.
GRM6-40.5 Series switchgears are suitable for control, protection and monitoring of 40.5 kV, three-phase, single busbar electrical system, widely used in generating companies, mining, etc.

Overview

GSRM6-40.5 33KV 36KV Series are a new type SF6 gas-insulated compact switchgears. Circuit breakers, disconnectors, and other parts are enclosed in 3mm-thick metal containers filled with a low-pressure SF6 gas. Thus, the equipment is compact, reliable, and safe; free of environmental impacts, free maintenance and long service life, etc.
GRM6-40.5 Series switchgears are suitable for control, protection and monitoring of 40.5 kV, three-phase, single busbar electrical system, widely used in generating companies, mining, etc.

Applicable Standars

IEC 62271-1:High-voltage switchgear and controlgear-Part 1: Common specifications
IEC 62271-100 :High-voltage switchgear and controlgear–Part 100: Alternating-current circuit-breakers
IEC 62271-102 High-voltage switchgear and controlgear–Part 102: Alternating current disconnectors and earthing switches
IEC 62271-103 High-voltage switchgear and controlgear–Part 103: Switches for rated voltages above 1 kV and up to and including 52 kV
IEC 62271-105 High-voltage switchgear and controlgear–Part 105: Alternating current switch-fuse combinations
IEC 62271-200:High-voltage switchgear and controlgear–Part 200: AC metal-enclosed switchgear and controlgear for rated voltage above 1kV and up to and including 52 kV
IEC 60044-2:Instrument transformers–Part 2: Inductive voltage transformers
IEC 60044-1:Instrument transformers–Part 1:Current transformers

Use Conditions

Altitude: ≤4000m★
Ambient air temperature: -25℃~+40℃;
Relative air humidity: daily average ≤95%, monthly average ≤90%;
Seismic intensity ≤8 class;
Places free from fire, explosion, serious contamination, chemical corrosion and severe vibration.
Note★: The manufacturer must be consulted in advance if site altitude is over 1000 m so as to adjust the inflation pressure.

Model meaning

 

Technical Parameters

No.DescriptionsUnitValue
1Rated voltagekV33  36  40.5
2Rated frequencyHz50 60
3Rated continuous currentA630  1250
4Rated
insulation
level (Ud,
Up, )
Power
frequency
withstand
voltage(Ud)
(1min)
Between phase and phase to earthkV95
Across the isolating distancekV118
Auxiliary and control circuits (Ua)kV2
Lightning
impulse
withstand
voltage (Up)
Between phase and phase to earthkV185
Across the isolating distancekV215
5Rated short-time withstand current (Ik/tk)kA/s25/4 , 31.5/4
6Rated peak withstand current (Ip)kA63, 80
7Rated short-circuit breaking current (Isc)kA25, 31.5
8Rated short-circuit making currentkA63, 80
9Circuit breaker electrical endurance/30 times
10Rated operating sequence./O-0.3s-CO-180s-CO
11Mechanical enduranceCircuit breakerOps20000
Disconnectors/Earthing switchesOps5000
12Resistance of the circuit630AμΩ≤120
1250AμΩ≤80
13Rated gas- filled pressure (the pressure at 20 °C)MPa0.02
14Annual leakage rate (relative pressure)/≤0.01%
15Isolation medium/SF6
16Degree of protection
(IP)
Isolation medium/IP2XC
Gas tank/IP67
Enclosure/IP41
Enclosure/IK10
17Classification IAC and Internal IAC/A-FLR , 31.5 kA 1s

Outline dimension