13.8kV Medium Voltage Switchgear/ Air Insulated Metal Clad Switchgear

13.8kV Medium Voltage Switchgear/ Air Insulated Metal Clad Switchgear

13.8kV Medium Voltage Switchgear

The switchgear and main apparatus contained in it comply with the latest IEC Standards:
• IEC 62271-1 for general purposes
• IEC 62271-200 for the switchgear
• IEC 62271-102 for the earthing switch
• IEC 62271-100 for the circuit-breakers
• IEC 60071-2 for the insulation coordination
• IEC 62271-106 for the contactors
• IEC 60265-1 for the switch-disconnectors
• IEC 60529 for degree of protections

13.8kV Medium Voltage Switchgear

The switchgear and main apparatus contained in it comply with the latest IEC Standards:
• IEC 62271-1 for general purposes
• IEC 62271-200 for the switchgear
• IEC 62271-102 for the earthing switch
• IEC 62271-100 for the circuit-breakers
• IEC 60071-2 for the insulation coordination
• IEC 62271-106 for the contactors
• IEC 60265-1 for the switch-disconnectors
• IEC 60529 for degree of protections

Service environment:
a) Air temperature:Maximum temperature: +40℃; Minimum temperature:-25℃

  1. b) Humidity:Monthly average humidity 95%; Daily average humidity 90% .
  2. c) Altitude above sea level:Maximum installation altitude: 2500m
  3. d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
  4. e) No frequent violent shake
Rated voltagekV13.8
Rated insulation voltagekV17.5
Rated power frequency withstand voltagekV 1min68
Rated lightning impulse withstand voltagekV95
Rated frequencyHz50/60
Rated short time withstand currentkA 3 sup to 50
Peak currentkAup to 125
Internal arc withstand currentkA 1sup to 50
Main busbar rated currentAup to 4000
Circuit-breaker rated currentA630

1250

1600

2000

2500

3150

Circuit-breaker rated current with forced ventilationA3600

4000

 

DescriptionUnitValue
Rated voltagekV13.8
Rated short-time power frequency withstand voltage (1min)(1min)68
Rated lightning impulse withstand voltage (peak)95
Rated freqHz50,60
Rated currentA630630125016001250160016002000
12501250200025002000250025003150
315031504000*4000*
Rated short-circuit drop-out currentkA202531.54050
Rated short time withstand current202531.54050
Rated short time continual times4
Rated peak withstand currentkA506380100125
Rated short-circuit closing current506380100125
Rated single/ back-to-back capacitor bank drop-out currentA630/400(40kA is 800/400)
Rated capacitor bank closing inrush currentkA12.5(frequency no more than 1000Hz)
Opening time (rated volt.)ms20~50
Closing time (rated volt.)35~70
Mechanical lifeTimes30,000
Rated break times for rated short drop out current50
Rated operation voltageVAC110/220 DC110/220
Rated current of power storing motorW70
Average opening speedm/s0.9~1.3
Average closing speed0.4~0.8
Rated operation procedureopening-0.3s-closing opening-180s-closing opening

Fully type-tested

The switchgear has undergone all the tests required by the international (IEC) Standards. Each switchgear unit is subjected to routine tests in the factory before delivery. These tests are intended to provide a functional check of the switchgear based on the specific characteristics of each installation.

IEC type tests
• Short-time and peak withstand current
• Temperature rise
• Internal arc capability
• Dielectric test
• Making and breaking capacity of circuit-breaker
• Earthing switch making capacity (top application)
• Mechanical operations of circuit-breaker and line
disconnector
• IP degree and impact test
IEC routine factory tests
• Visual inspection and check
• Mechanical sequence operations
• Cabling check
• Electrical sequence operations
• Power frequency withstand voltage
• Measurement of the resistance of the main circuits
• Secondary insulation test
The enclosure is made of aluminium-zinc plated steel sheet by CNC machine, high precise dimension, short production cycle, excellent mechanical strength and nice appearance. The busbar compartment, VCB handc art compartment, cable compartment and relay compartment are separated by metal sheet. Flexible operation for handcart movement, clear position instruction, the earthing switch allow to making short circuit current and creditable mechanical interlock.